top of page
VM Group Srl logo - ventilated facades

Technical Portal for Sustainable Architecture

How is wind load resistance ensured?

Wind action represents the most critical dynamic stress for the structural integrity of a ventilated façade. Unlike vertical static loads, which are governed by gravity, wind acts orthogonally to the surface of the building envelope, alternating cycles of pressure and strong vacuum (suction).

To ensure the static safety of the structure, the façade system—comprising cladding, mechanical fixings, substructure, and wall anchors—must be sized to safely transfer these kinematic stresses to the building's load-bearing structure, complying with the requirements of current regulations (NTC 2018 and Eurocode 1).

Wind action on the envelope: pressure and suction dynamics

Determining the wind load on the façade is not limited to calculating peak velocity pressure, but requires a detailed analysis of the building's geometry. Wind action manifests itself in two ways:

  • Positive pressure: It acts on the windward façades, pushing the cladding toward the interior of the building.

  • Negative pressure: It occurs on the leeward façades and, with extremely violent localized peaks, at the corners and perimeter edges of the building (corner areas). This latter stress is the most dangerous, as it tends to "tear" the cladding panels and substructure profiles outward.

Calculation and modeling criteria according to the NTC 2018

Wind load calculations must strictly follow the Technical Standards for Construction (NTC 2018). The designer must determine the wind pressure (p) by considering a combination of several factors:


p = q_b x c_e x c_p x c_d


Where q_b is the base velocity pressure (depending on the geographic area and altitude), c_e is the exposure coefficient (related to the building's height above ground and the terrain roughness category), c_p is the shape or aerodynamic coefficient (which differentiates central areas from corner areas), and c_d is the dynamic coefficient.

Using the correct c_p coefficients for perimeter areas is essential to avoid underestimating the suction effect on the edges.

Sizing and spacing of vertical uprights

Once the Ultimate Limit State (ULS) design loads have been determined, the substructure profiles (usually aluminum "T" or "L" mullions) are sized.

The mullion's resistance is verified for bending and flexural buckling under the action of pressure and vacuum. To limit the maximum allowable deflection of the profile (usually constrained to L/200 or L/300 of the spacing between the supports), the designer defines the spacing of the mullions and the spacing of the wall anchoring brackets.

In corner areas, where negative pressures are greater, the spacing of the mullions is significantly reduced compared to the central areas of the façade.

Sheet metal fastening systems: clips, rivets and back-of-sheet anchors

Wind load is transferred from the exterior cladding panel to the studs through the fastening systems, which can be exposed or concealed. Each fastening point must be tested for two main failure modes:

  • Pull-out failure: The suction force of the wind tends to tear the rivet or clip from the aluminum profile, or the back-panel anchor (such as Keil or Invisio) from the body of the panel.

  • Bending or punching failure of the panel: The panel itself, under wind stress, experiences stress concentrations at the fastening holes. Panel manufacturers (stoneware, fiber cement, or HPL) provide characteristic strength values ​​that determine the minimum number of fastenings per square meter based on the design pressure.

Anchoring to the load-bearing structure: choosing the right anchors and pulling-out tests

The final link in the static chain is the anchoring of the metal brackets to the supporting wall (concrete, solid brick, perforated brick, or lightweight infill).

Wind load resistance at this point is ensured by the correct selection of anchors (mechanical expansion anchors or weakly prestressed chemical injection anchors).

Since the quality and mechanical strength of the masonry substrate can vary significantly (especially during renovation projects), it is best practice to perform in-situ pull-out tests directly on the building's masonry to experimentally validate the anchor's load-bearing capacity before proceeding with the final calculation.

test pull out
icona telefono
VM Group Srl logo - ventilated facades

VM Group Srl is a leader in the design and installation of advanced building envelope systems. With over 30 years of experience, the company specializes in multi-material ventilated facades (HPL, fiber cement, ceramic, metals) and high-performance thermal and fire safety solutions (Class A1). A partner of leading international brands (Equitone, Trespa, Laminam), VM Group operates nationwide in the healthcare, education, retail, and luxury residential sectors.

Registered office

VM Group Srl
Foro Traiano 1/a
00187 Rome (RM)
VAT No. IT 02303290569
Share Capital €110,000.00
ESCo Certified UNI CEI 11352:2014
ISO 9001:2015 Certified

Headquarters

Via dell'Industria, snc

01100 Viterbo - Italy

VM Point Bologna

Via Tommaso Martelli 25 A

40138 - Bologna - Italy

Social

  • LinkedIn
  • YouTube

© 2025 by VM Group - ventilated facades

bottom of page